With a Heat only Boiler 39 POINT INSPECTION With Full Strip Down we...
CHECK
-
Check Room thermostat batteries.
-
Check/ lubricate fan bearings.
-
Check condition of burners.
-
Check condition of heat Exchanger.
-
Check for water leaks.
-
Operation of all safety controls.
-
Check Pumps for Leaks, Noisy , Amperage.
-
Condensate pipe lines clean if needed.
​
​
​
​
​
​
INSPECT
-
Gas piping for pressure tag and certification , bonding & Correct size.
-
Exhaust and air intake is correct, materials used, Size and vented correctly & correct slope.
-
Flame Picture is correct.
-
Boiler / Controls wiring, loose, worn.
-
For Paints flammable chemicals in same area as boiler.
TEST
-
Exhaust fan motor amps
-
Delta T Heat rise across supply and return.
-
Burner Flame sensor take results record.
-
Safety Controls NTC , overheat, flue sensor
-
Ignition (Condition & ohms ) Change if needed.
-
Condensate Pump
-
Gas Analyzation High and Low (Emissions / Efficiency and tests for Defective heat Exchanger.)
-
Carbon monoxide alarm
-
Boiler water Glycol Percentage 35%
-
Boiler water PH Levels should be 8.5
-
Test alkalinity Level should be 140-700 PPM
-
Boiler water Iron Levels 2ug/L or less
-
Boiler Water TDS 2000PPM
-
Total water Hardness 0.01 to 2.0PPM
​
CLEAN
-
Boiler Filters Including Mag filter.
-
Flame Sensor / Ignition rods.
-
Burners
-
Clean strip Fan if needed.
-
Fire Side Heat Exchanger clean, brush, Flush, Descale with Vinegar condensate.
-
Condensate trap, and pipework.
-
condensate pump.
-
General wipe down.
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
IDENTIFY
-
System Breaker switch
-
Make model and serial Number of Boiler add to profile.
-
Age of Boiler
-
Any Infractions of the Gas safety code.
​
​
​
​
​
​
​
​
​
​
​
​